Snow Melt System Calculator

Design hydronic snow melting systems per ASHRAE guidelines.

Area Information

Climate Conditions

System Configuration

Fluid Temperatures

ASHRAE Snow Melt Classifications

ClassBTU/sq ftApplication
I75-100Residential, Intermittent
II100-150Commercial, Continuous
III150-250Critical Safety Areas

Design Guidelines

Minimum Glycol: 30% for freeze protection to -10F

Surface Temp: Target 35-40F during snow

Pre-heat: Start system before snowfall

Insulation: R-5 minimum below slab